What are the troubleshooting methods for combustible gas detectors

Aug 10, 2023

Leave a message

What are the troubleshooting methods for combustible gas detectors

 

(1) Identify the potential leakage points of the device to be monitored, analyze their leakage pressure, direction, and other factors, and draw a distribution map of probe positions. According to the severity of the leakage, it is divided into three levels: I, II, and III.


(2) Based on specific factors such as airflow direction and wind direction in the location, determine the direction of flammable and toxic gas leakage when a large amount of leakage occurs.


(3) Based on the density of the leaked gas (greater than or less than air), combined with the trend of air flow, a three-dimensional flow trend map of the leak is synthesized, and an initial point plan is made at the downstream position of its flow.


(4) Study whether the leakage state of the leakage point is micro leakage or jet like. If it is a slight leak, the location of the point should be closer to the leak point. If it is a jet leakage, it should be slightly away from the leakage point. Based on these conditions, a final site setting plan has been formulated. In this way, the quantity and variety to be purchased can be estimated.


(5) For places with significant combustible gas leakage, a detection point should be set up every 10-20 meters according to relevant regulations. For small and discontinuous pump rooms that are not on duty, attention should be paid to the possibility of combustible gas leakage. Generally, a detector should be installed at the lower air outlet.


(6) For places with hydrogen leakage, the detector should be installed on the plane above the leakage point.


(7) For media with a gas density greater than air, the detector should be installed on a plane below the leakage point, and attention should be paid to the characteristics of the surrounding environment. For places prone to the accumulation of combustible gases, special attention should be paid to the setting of safety monitoring points.


(8) For an open environment where flammable and toxic gases diffuse and escape, if there is a lack of good ventilation conditions, it is easy to make the content of flammable and toxic gases in the air of a certain location close to or reach the lower limit concentration. These are safety monitoring points that cannot be ignored.

 