Introduction to Precautions for Using Clamp Meters

Nov 26, 2026

Introduction to Precautions for Using Clamp Meters

 

① When measuring on high‑voltage circuits, it is forbidden to attach extra leads to the clamp ammeter for measurement. When measuring the current of each phase of a high‑voltage cable, the clearance between cable terminals shall be more than 300 mm with good insulation; measurement can only be carried out when the setup is convenient.

 

② When reading the meter, pay special attention to maintaining a safe distance between your head and live parts. The distance between any part of the human body and live conductors shall not be less than the overall length of the clamp meter.

 

③ When measuring the current of low‑voltage fuses or horizontally arranged low‑voltage busbars, isolate each phase fuse or busbar with insulating materials before measurement to prevent phase‑to‑phase short circuits.

 

④ When using a high‑voltage clamp ammeter, pay attention to its voltage class. It is strictly prohibited to use a low‑voltage clamp meter to measure current in high‑voltage circuits. Measurements with a high‑voltage clamp meter shall be performed by two persons. Non‑on‑duty operators shall fill out a Category 2 work permit. Wear insulating gloves and stand on an insulating mat during measurement. Do not touch other equipment to avoid short circuits or earth faults.

 

⑤ After finishing measurement with the clamp ammeter, turn the switch to the maximum range to prevent accidental overcurrent in the next use, and store the instrument in a dry room.

 

⑥ Measurement is strictly forbidden when one phase of the cable is earthed. This prevents earth breakdown and explosion caused by poor insulation at cable terminals, which endangers personal safety.

 

⑦ When measuring with a clamp meter, currents from adjacent conductors may cause interference. Therefore, keep the three‑phase conductors evenly spaced.

 

⑧ Since the clamp ammeter is used near energized circuits, check its insulation performance before use. Ensure the housing is free of damage and the handle is clean and dry.

 

⑨ A clamp ammeter cannot measure the current of bare conductors.

 

⑩ It is forbidden to switch the range of the clamp ammeter during measurement. If range switching is required, withdraw the conductor from the jaws first before changing the range.

 

Clamp meter -