Introduction to Clever Use of a Multimeter for Measuring Earth Resistance
In many applications, grounding electrodes and grounding leads need to be installed for reliable earthing of instruments and equipment. Specialized earth resistance testers (such as the Hioki 4105A made in Japan) are normally used to verify that the earth resistance meets specifications.
However, dedicated earth resistance testers are expensive and not readily available in practical work. Is it possible to measure earth resistance with a multimeter? The author carried out earth resistance tests with a multimeter in soils of different textures and compared the readings with those from a professional earth resistance tester. The results show good agreement. The measurement procedure is described below:
Prepare two round steel bars of 8 mm diameter and 1 m length. Sharpen one end of each to serve as auxiliary test probes. Drive them into the ground on both sides of the test electrode A, 5 m away from A, to a depth of at least 0.6 m. Keep A, B and C in a straight line.
Here, A is the electrode under test; B and C are auxiliary test probes.
Use the R×1 range of the multimeter to measure the resistance between A and B, and between A and C. Record the readings as Rₐᵦ, Rₐc and Rᵦc respectively. The earth resistance of electrode A can then be calculated.
Earth resistance is defined as the contact resistance between the grounding electrode and surrounding soil. Let Rₐ, Rᵦ, Rc = earth resistances of electrodes A, B and C; Let Rₓ = soil resistance between A and B. Since the distance AC equals AB, the soil resistance between A and C is also Rₓ. As BC = 2AB, the soil resistance between B and C is approximately 2Rₓ.
We obtain the equations: Rₐᵦ = Rₐ + Rᵦ + Rₓ ① Rₐc = Rₐ + Rc + Rₓ ② Rᵦc = Rᵦ + Rc + 2Rₓ ③
Combine ① + ② − ③: Rₐ = (Rₐᵦ + Rₐc − Rᵦc) / 2 ④
Equation ④ is the formula for calculating the earth resistance.
Practical example: Measured values for a grounding electrode: Rₐᵦ = 8.4 Ω, Rₐc = 9.3 Ω, Rᵦc = 10.5 Ω Rₐ = (8.4 + 9.3 − 10.5) / 2 = 3.6 (Ω)
Therefore, the earth resistance of electrode A under test is 3.6 Ω.
Important note: Before measurement, polish the surfaces of electrodes A, B and C with sandpaper to minimize contact resistance between test probes and electrodes and reduce measurement error.