Clamp ammeters are divided into high-voltage and low-voltage types, used for direct current measurement on circuits without disconnecting the wiring. The operating instructions are as follows:

 

① When using a high‑voltage clamp meter, pay attention to its voltage class. It is strictly forbidden to use a low‑voltage clamp meter to measure current in high‑voltage circuits. High‑voltage clamp meter measurement shall be performed by two operators. If the operator is not on duty, a Category 2 work permit shall be filled out. Wear insulating gloves and stand on an insulating mat during measurement. Do not touch other equipment to prevent short circuit or earth fault.

 

② When reading the meter, maintain a safe distance between your head and live parts. The distance between any part of your body and live conductors shall not be less than the full length of the clamp meter.

 

③ When measuring on high‑voltage circuits, it is forbidden to connect the meter with extra leads from the clamp ammeter. For current measurement of each phase of high‑voltage cables, the clearance between cable terminals shall be more than 300 mm with good insulation. Measurement can only be carried out when the setup is convenient for testing.

 

④ When measuring the current of low‑voltage fuses or horizontally arranged low‑voltage busbars, insulate and isolate each phase fuse or busbar with insulating materials before measurement to avoid phase‑to‑phase short circuit.

 

⑤ Measurement is strictly prohibited when one phase of the cable is earthed. This prevents earth breakdown and explosion caused by poor insulation at cable terminals, which may endanger personal safety.

 

⑥ After measurement, turn the switch of the clamp ammeter to the maximum range to avoid accidental overcurrent in next use; store the instrument in a dry indoor place.

 